Advisory Details

January 14th, 2019

Schneider Electric IIoT Monitor downloadCSV Directory Traversal Information Disclosure Vulnerability

ZDI-19-020
ZDI-CAN-7118

CVE ID CVE-2018-7835
CVSS SCORE 7.5, AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N
AFFECTED VENDORS Schneider Electric
AFFECTED PRODUCTS IIot Monitor
VULNERABILITY DETAILS

This vulnerability allows remote attackers to disclose sensitive information on vulnerable installations of Schneider Electric IIoT Monitor. Authentication is not required to exploit this vulnerability.

The specific flaw exists within downloadCSV.jsp servlet. The issue results from the lack of proper validation of a user-supplied path prior to using it in file operations. An attacker can leverage this vulnerability to disclose sensitive information in the context of SYSTEM.

ADDITIONAL DETAILS Schneider Electric has issued an update to correct this vulnerability. More details can be found at:
https://ics-cert.us-cert.gov/advisories/ICSA-19-008-02
DISCLOSURE TIMELINE
  • 2018-08-14 - Vulnerability reported to vendor
  • 2019-01-14 - Coordinated public release of advisory
CREDIT rgod of 9sg Security Team - rgod@9sgsec.com