CVE ID | CVE-2018-7836 |
CVSS SCORE | 7.2, AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H |
AFFECTED VENDORS |
Schneider Electric |
AFFECTED PRODUCTS |
IIot Monitor |
VULNERABILITY DETAILS |
This vulnerability allows remote attackers to execute arbitrary code on vulnerable installations of Schneider Electric IIoT Monitor. Authentication is required to exploit this vulnerability but authentication can be easily bypassed. The specific flaw exists within the processing of the upload method of the ProtectionMgmt servlet. The issue results from the lack of proper validation of a user-supplied path prior to using it in file operations. An attacker can leverage this vulnerability to execute code in the context of SYSTEM. |
ADDITIONAL DETAILS |
Schneider Electric has issued an update to correct this vulnerability. More details can be found at:
https://ics-cert.us-cert.gov/advisories/ICSA-19-008-02 |
DISCLOSURE TIMELINE |
|
CREDIT | rgod of 9sg Security Team - rgod@9sgsec.com |