CVE ID | CVE-2018-18988 |
CVSS SCORE | 5.0, AV:N/AC:L/Au:N/C:P/I:N/A:N |
AFFECTED VENDORS |
LAquis SCADA |
AFFECTED PRODUCTS |
Software |
VULNERABILITY DETAILS |
The specific flaw exists within the processing of the MemoryReadByte method. The issue results from the lack of proper validation of a user-supplied value prior to dereferencing it as a pointer. An attacker can leverage this in conjunction with other vulnerabilities to execute code in the context of the aq process. |
ADDITIONAL DETAILS |
LAquis SCADA has issued an update to correct this vulnerability. More details can be found at:
https://ics-cert.us-cert.gov/advisories/ICSA-19-015-01 |
DISCLOSURE TIMELINE |
|
CREDIT | Esteban Ruiz (mr_me) of Source Incite |