CVE ID | CVE-2022-41779 |
CVSS SCORE | 8.8, AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H |
AFFECTED VENDORS |
Delta Electronics |
AFFECTED PRODUCTS |
InfraSuite Device Master |
VULNERABILITY DETAILS |
This vulnerability allows remote attackers to execute arbitrary code on affected installations of Delta Industrial Automation InfraSuite Device Master Device-Monitor. User interaction is required to exploit this vulnerability in that the target client must connect to a malicious server. The specific flaw exists within the DeSerializeBinary function. The issue results from the lack of proper validation of user-supplied data, which can result in deserialization of untrusted data. An attacker can leverage this vulnerability to execute code in the context of the current user. |
ADDITIONAL DETAILS |
Delta Electronics has issued an update to correct this vulnerability. More details can be found at:
https://www.cisa.gov/uscert/ics/advisories/icsa-22-298-07 |
DISCLOSURE TIMELINE |
|
CREDIT | kimiya |